Investigation of electrical energy quality of Muş Alparslan University campus
Is this your thesis?
This record came from a bulk archive import. If it’s yours, link it to your profile.
Abstract (EN)
In this thesis, the distribution transformers on the Muş Alparslan University campus have been examined for power quality issues related to current and voltage harmonics. Measurements of current and voltage harmonics were recorded using an energy analyzer at the transformers on the campus. The obtained current and voltage harmonics were analyzed. The measurements revealed that the current harmonics were above the standard limits, while the voltage harmonics were within the standard limits. Using the current harmonic values, three-phase nonlinear load models were created in the Matlab/Simulink environment. The total harmonic distortion (THD) ratios of these models were found to be quite close to the values measured by the energy analyzer. A parallel active power filter designed to eliminate current harmonics was developed in Matlab/Simulink, and the performance of the parallel active power filter was evaluated for each transformer.
Author
Nejdet Sezgin
How to Cite
Nejdet Sezgin (Master Thesis). Investigation of electrical energy quality of Muş Alparslan University campus, 2024, Bitlis Eren University.
Keywords
License
Tüm Hakları Saklıdır
This work is shared under the specified license terms.
More theses from Bitlis Eren University
- Determination of radon levels in some medicine and aromatic plants growing in Bitlis(2016)
- The ingratitude of the Israelites and Kiptians in the story of prophet Moses(2025)
- Mubhamatu'l-Qur'an in Tabari's tafsir(2025)
- Concepts of qirāʾāt in the works of Muhammad Alī al-Sābūnī(2025)
- Adilcevaz Kef Castle in the light of new archaeological research and geophysical investigations(2019)
- Transcryption and analysis of numbered 2782 Muslim Population Registers of Kars village Kagizman sanjak Kagizman town and kaza of Geçvan(2020)