Abstract (EN)
SUMMARY Master Thesis THE INVESTIGATION OF HEAT TRANSFER AND PRESSURE DROP TN THE HEAT EXCHANGERS EQUIPPED TURBULANCE GENERATOR WITH IN JEKTOR AT THE ENTRANCE SECTION Gülşah ÇAKMAK University of Fırat Gradute School of Natural and Applied Science Department of Mechanical Engineering 2000, Page: 100 In this work, undertaken to enhance heat transfer rates, swirling motion was imposed on the hot air by placing injektors(swirl elements) with various diameter and number of circular slots in straight or zig-zag line rows on the entrance section of a inner pipe of concentric tube heat exchanger with this aim various swirl generators(injectors) were prepared to test in the experiments. These elements are lid-shaped parts containing different diameter and number of circular slots and can be placed and removed eaisly on the entance section of the inner pipe. Hot air and cold'water were passed though the inner pipe and annulus respectively. Experiments were carried out for both parallel and countercurrent flow models of the fluids at Reynolds numbers.VI Heat transfer rates increased with decresing diameter and with increasing number of slots the swirl elements(injectors) used in the experiments. Additional enhancements aquied with slots arranged in zig-zag line. The highest enhancement was seen to occur in countercurrent flow mode of exchanger with swirl elements having smaller diameter five slots in a row of zig-zag line. The additional flow energy required to overcome the loves in the entrance section of the inner pipe was found to be very much lower than net heat gain aquired with swirl elements. The results showed that up to % 190 enhancement could be accomplished in heat transfer rates with this kind of swirl generators compared to heat exchanger without these elements. In the end of the study, the results showed that a rather smaller size but the same capasity heat exchanger could be proposed by using these elements improsing swirling to the fluid flowing through inner pipe. Key Words: Heat exchanger, Swirling flow, Injector.
Author
Gülşah Çakmak
How to Cite
Gülşah Çakmak (Master Thesis). The Investigation of heat transfer and pressure drop in the heat exchangers equipped turbulance generator with injektor at the entrance section, 2000, Fırat University.
License
Tüm Hakları Saklıdır
This work is shared under the specified license terms.
More theses from Fırat University
- Using social media as an integrated marketing communication tool(2018)
- Foundation of Dutch East İndia Company and her rising in İndonesia in the 17th century(2013)
- Examination of stress state between Doğanyol (Malatya) and Çelikhan (Adıyaman) on the east Anatolian fault zone(2020)
- Color usage at Turkish Divan of Fuzûlî(2013)
- Yavuzeli (Gaziantep) surrounding volcanic outcropping of rocks petrographic and geochemical features(2014)
- Hizbu?t-Tahrir and the religions and political thoughts of Ercumend Özkan(2008)